Series 5000 Entry System Installation/Operation Manual
3-10 151174
3.5.6 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring
configurations.
3.5.6.1 Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum
wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel,
it is necessary to calculate the total worst case current draw for all modules on a single
4-conductor bus. The total worst case current draw is calculated by adding the individual
worst case currents for each module. The individual worst case values are shown in the table
below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp.
After calculating the total worst case current draw, Table 3-2 specifies the maximum distance
the modules can be located from the panel on a single wire run. The table insures 2.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
Model Number Worst Case Current Draw
5083 .200 amps
5084 .200 amps