SILENT KNIGHT INTELLIKNIGHT 5808 Dokumentacja Strona 96

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 95
Programming 151274-L8
7-4
3. Press 2 to enter zone menu.
4. Press 1 to edit a zone.
5. Enter the zone number, then press
ENTER.
7.3.1.1 Edit Zone Name
6. Press 1 to edit the selected zone’s name.
A screen similar to the one shown in Figure 7-2 displays.
Figure 7-2 Selecting Character for Zone Name
7. Select the characters for the zone name by pressing the or arrow until the desired character is shown
then press . or See Appendix B of this manual for a list of available characters and their numeric designa-
tors.
8. Repeat step 8 until the name is complete.
9. Press
ENTER when the name is complete.
7.3.1.2 Edit Zone Properties
Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1. Do steps 1 through 5 of Section 7.3.1.
2. Press 2 to edit the properties of the selected zone.
Figure 7-3 Editing Zone Properties
Alarm Delay Characteristics
3. Select the alarm delay characteristics by pressing the or arrow.
Detection type also selected from
this screen (see Table 7-1).
Przeglądanie stron 95
1 2 ... 91 92 93 94 95 96 97 98 99 100 101 ... 179 180

Komentarze do niniejszej Instrukcji

Brak uwag