Installation andOperations ManualINTELLIKNIGHT®MODEL 5808Addressable Fire Control PanelDocument 151274-L810/30/14 Rev: VP/N 151274-L8:V E

Strona 2 - Installation Procedure

IntelliKnight 5808 Installation Manual 151274-L81-21.2 About this ManualThis manual is intended to be a complete reference for all installation and op

Strona 3 - Contents

Programming 151274-L87-87.3.1.4 Cadence PatternsThe cadence patterns shown in Figure 7-6 are available for use with the control panel. Cadence pattern

Strona 4 - Section 5

IntelliKnight 5808 Installation Manual 151274-L87-97.3.1.5 Zone Accessory OptionsThis option applies to detectors that are used with Sounder bases or

Strona 5 - Section 7

Programming 151274-L87-107.4 GroupAn output group is made up of output points that have been programmed to respond in the same way. Output groups simp

Strona 6

IntelliKnight 5808 Installation Manual 151274-L87-11• Operation with system switches.Figure 7-9 Group Properties Screen Programming OptionsLatching /

Strona 7

Programming 151274-L87-123. To get to this menu item repeat steps 1 through 6 of section 7.4.1.4. To edit group properties, press 2.5. Press the or

Strona 8

IntelliKnight 5808 Installation Manual 151274-L87-13A warning screen will display. If you want to proceed with deleting the group, select Yes. To canc

Strona 9 - Introduction

Programming 151274-L87-145. Select output group number. See Figure 7-10.Figure 7-10 Output Group Template Programming Screen7.5 PointYou may need to

Strona 10 - 1.2 About this Manual

IntelliKnight 5808 Installation Manual 151274-L87-158. Select the function of the device by pressing the or arrows. Refer to Table 7-5 under colum

Strona 11 - 1.3 Compatible Products

Programming 151274-L87-16SLC LoopCO SMOKE DETECTORALRM CO/ALRM FIRESUP CO/ALRM FIREALRM CO/SUP FIRESUP CO/SUP FIRELatching Supervisory switches can be

Strona 12 - Manufacturer Model

IntelliKnight 5808 Installation Manual 151274-L87-17SLC(cont.)SWITCH(cont.)PAS_ACK Positive acknowledge switch. This switch must be used in zones prog

Strona 13

Introduction 151274-L81-31.3 Compatible ProductsThe chart below lists the products available from Silent Knight for use with the 5808.Note: 5865-3, 58

Strona 14

Programming 151274-L87-187.5.2 Point Programming For Internal or External Power ModuleTo program for an internal or external power module points, foll

Strona 15 - Section 2

IntelliKnight 5808 Installation Manual 151274-L87-1910. Repeat Steps 1 through 15 for all circuits.Table 7-6 Menu Choices for Internal/External Power

Strona 16

Programming 151274-L87-207.5.3 Point Programming For 5880 and 5865 ModulesTo program 5880 or 5865 module points:1. Enter the installer code.2. Select

Strona 17 - Systems

IntelliKnight 5808 Installation Manual 151274-L87-215. Select the characters for the point name by pressing the or arrow until the desired charact

Strona 18 - Before You Begin Installing

Programming 151274-L87-22Select Account (ID)The control panel provides up to 4 reporting accounts. The priority of an account is based on its account

Strona 19 - 3.3 Electrical Specifications

IntelliKnight 5808 Installation Manual 151274-L87-23account. Range is 3-5.11. Enter the number of switch attempts (or press the or arrow), then pr

Strona 20 - 3.4 Wiring Specifications

Programming 151274-L87-243. From the Program Menu, select 5 for System Options.4. Select 1 for the phone lines menu.5. Select the phone line to be edi

Strona 21 - 3.5 Board Assembly Diagram

IntelliKnight 5808 Installation Manual 151274-L87-257.6.2.4 Rotary Format9. Press the or arrow to select the pulse ratio for rotary dialing option

Strona 22

Programming 151274-L87-26Figure 7-16 System Trouble Event Mapping Example7.6.3.2 System Alarm CadenceFire drill and system auxiliary alarm events can

Strona 23

IntelliKnight 5808 Installation Manual 151274-L87-276. Select the holiday schedules you wish to edit (1- holidays 1 - 9, 2- holidays 10 - 18).Figure 7

Strona 24

IntelliKnight 5808 Installation Manual 151274-L81-4The following modems have been tested by Silent Knight for compatibility with the 5808 and the Sile

Strona 25

Programming 151274-L87-286. Enter the desired number of seconds for the alarm verification time. 7. Press or ENTER to make your selection and move to

Strona 26

IntelliKnight 5808 Installation Manual 151274-L87-29Note: The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.

Strona 27 - Warning!

Programming 151274-L87-30revert to standard time on the last Sunday in October at 2:00 a.m. After January 2007, if this feature is enabled, the system

Strona 28

IntelliKnight 5808 Installation Manual 151274-L87-31A screen similar to the one shown in Figure 7-21 will display. Figure 7-21 Intern

Strona 29

Programming 151274-L87-327.7 JumpStart AutoprogrammingTo run JumpStart:1. Enter the installer code.2. Select 7 for Program Menu.3. Select 6 for System

Strona 30 - Control Panel Installation

IntelliKnight 5808 Installation Manual 151274-L87-33Table 7-8 lists the panel functions that can be selected for each user profile. To change an a

Strona 31 - 4.3 Battery Connection

Programming 151274-L87-34Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the user name and

Strona 32 - 4.3.1 RBB Accessory Cabinet

151274-L88-1Section 8System OperationOperation of the control panel is simple. Menus guide you step-by-step through operations. This section of the ma

Strona 33

System Operation 151274-L88-28.2.1 LCD DisplaysThe control panel LCD displays system messages, annunciates alarms, supervisories and troubles; provide

Strona 34 - 4.4 SBUS Wiring

IntelliKnight 5808 Installation Manual 151274-L88-38.4 Menu SystemThe control panel is easy to operate from Main Menu. To view the Main Menu press the

Strona 35

Introduction 151274-L81-5falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect

Strona 36 - 4.4.2 Wiring Configurations

System Operation 151274-L88-48.4.2 Using the Menus8.5 Basic Operation8.5.1 Setting Time and Date1. From the Main Menu, select 4 for Set Date and Time.

Strona 37

IntelliKnight 5808 Installation Manual 151274-L88-53. Select 7 for Disable/Enable Pt.4. Use and to move through the list. Press ENTER to select th

Strona 38 - 4.5.1 Mounting the 5860

System Operation 151274-L88-68.5.10 Conduct a Walk Test1. From the Main Menu, press 1 for System Tests.2. Select 3 for Walk Test-No Rpt. Enter the tim

Strona 39 - 4.5.1.1 Flush Mounting

IntelliKnight 5808 Installation Manual 151274-L88-78.5.14 Check Detector Sensitivity Through Point StatusThe control panel constantly monitors smoke d

Strona 40 - (outline)

System Operation 151274-L88-88.5.15 View Status of a Point1. From the Main Menu, select 2 for Point Status. 2. From the list that displays, press ENTE

Strona 41 - Installation

IntelliKnight 5808 Installation Manual 151274-L88-93. If you are using the panel’s internal modem to communicate, you will be prompted to enter a phon

Strona 42 - 4.6.1 Selecting 5824 Options

System Operation 151274-L88-10Note: Detector status can also be viewed and printed using the 5660 or 5670 (facility monitoring only) SKSS.8.6 Operatio

Strona 43 - 4.7 5880 LED I/O Module

IntelliKnight 5808 Installation Manual 151274-L88-11AlarmA smoke detector goes into alarm or a pull station is activated.CO detector goes into alarm.I

Strona 44 - 4.7.2 FACP Connection

System Operation 151274-L88-12SupervisoryThe system detects a supervisory condition.The system detects a supervisory condition with a CO detector.The

Strona 45 - 4.7.3 LED Wiring

IntelliKnight 5808 Installation Manual 151274-L88-13TroubleA system trouble condition occurs.A trouble condition with a CO detectorThe dialer seizes c

Strona 46 - 4.7.4 Dry Contact Wiring

IntelliKnight 5808 Installation Manual 151274-L81-6• Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended th

Strona 47 - 4.8.1 FACP Connection

System Operation 151274-L88-14Reset The RESET button is pressed followed by a valid code or rotation of the key.All LEDs are on briefly then the LCD d

Strona 48 - 4.8.2 5865 Mounting

IntelliKnight 5808 Installation Manual 151274-L88-158.7 Releasing OperationsThis control panel supports two types of releasing: Double Interlock Zone

Strona 49 - 4.9 Configuring Modules

System Operation 151274-L88-168.7.1 Single Interlock Zone ReleasingA single interlock zone utilizes a minimum of two addressable detectors, and a desi

Strona 50 - 4.10 Telephone Connection

IntelliKnight 5808 Installation Manual 151274-L88-178.7.2 Double Interlock Zone ReleasingA Double Interlock Zone uses a minimum of two Addressable det

Strona 51

System Operation 151274-L88-188.8 Smoke Alarm VerificationFigure 8-6 illustrates how the Smoke Alarm Verification cycle operates.Figure 8-6 Smoke Ver

Strona 52 - 4.11.2.1 Door Holder Power

151274-L89-1Section 9ReportingThis section lists receivers that are compatible with this control panel and the reporting codes sent by the control pan

Strona 53 - 4.11.2.4 Sounder Sync Power

Reporting 151274-L89-2Initial Power up Trouble RR 0 1 305 00 000Local Programming begin Trouble LB 0 1 627 00 000Local Programming ended normally Trou

Strona 54 - 4.12.2 Programmable Relays

IntelliKnight 5808 Installation Manual 151274-L89-3Voice VBUS Trouble1Trouble ET Exp. ID 1 332 00 Exp. IDVoice VBUS Trouble Restore1Trouble ER Exp. ID

Strona 55

Reporting 151274-L89-4Water release circuit has been disabledTrouble pi Exp. ID SS Point # 1 203 Exp. ID Point #Water release circuit has been re-enab

Strona 56

IntelliKnight 5808 Installation Manual 151274-L89-5Notification Trouble Trouble FT 1000+Group #1 320 00 Group #Notification Output trouble restore Tro

Strona 57

151274-L82-1Section 2Agency Listings, Approvals, and Requirements2.1 Federal Communications Commission (FCC)The following information must be provided

Strona 58

Reporting 151274-L89-6Zone-based AUX1 switch trouble restoreTrouble UJ 1000+ Zone # 3 373 01 Zone #Zone-based AUX2 switch trouble restoreTrouble UJ 20

Strona 59

IntelliKnight 5808 Installation Manual 151274-L89-7Emergency NAC Trouble Restored1Trouble pi Exp. ID QJ Point # 3 320 Exp. ID Point #Emergency Control

Strona 60

Reporting 151274-L89-8Positive Alarm sequence acknowledge switch troubleTrouble pi Exp. ID FT Point # 1 373 Exp. ID Point #Point Enabled Disable pi Ex

Strona 61

IntelliKnight 5808 Installation Manual 151274-L89-9Voice Aux Status Switch Disabled1Disable pi Exp. ID UB Point # 1 580 Exp. ID Point #Voice Aux Statu

Strona 62

151274-L810-1Section 10Testing and Troubleshooting10.1 TroubleshootingThis section of the manual offers suggestions for troubleshooting hardware probl

Strona 63 - 5.3 Maximum Number of Devices

Testing and Troubleshooting 151274-L810-210.2.1 Periodic Testing and MaintenanceTo ensure proper and reliable operation, it is recommended that system

Strona 64

IntelliKnight 5808 Installation Manual 151274-L810-310.2.2 Event HistoryThe event history can be useful for tracking or recalling a trouble condition.

Strona 65

Testing and Troubleshooting 151274-L810-4A message similar to the one shown in Figure 10-2 will display.Figure 10-2 Shut Down Warning3. Press the o

Strona 66 - 5.5 SK Detector Installation

IntelliKnight 5808 Installation Manual 151274-L810-510.4 Impedances that Cause Earth Ground FaultsTable 10-1 show the minimum impedances that cause an

Strona 67 - 5.7 SD Detector Installation

151274-L811-1Section 11Installation RecordsThis section of the manual is for you to use if you wish to track of how points, zones, and groups have bee

Strona 68 - 5.8 Addressing SD Devices

Agency Listings, Approvals, and Requirements 151274-L82-2installer.2.2 Underwriters Laboratories (UL)2.2.1 Requirements for All InstallationsGeneral r

Strona 69

Installation Records 151274-L811-2On-board 61 On-board 95On-board 62 On-board 96On-board 63 On-board 97On-board 64 On-board 98On-board 65 On-board 99O

Strona 70 - Programming Overview

151274-L8A-1Appendix ACompatible DevicesA.1 Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL

Strona 71 - ENTER to accept

Compatible Devices 151274-L8A-2Faraday446 Vibrating Bell 476 Vibrating Bell477 Single Stroke Bell2700 -M. -R, -T, -Y, -Z Strobe2701 Series Strobe2705

Strona 72

IntelliKnight 5808 Installation Manual 151274-L8A-3Faraday(cont.)5346 Electronic Horn with Strobe5347 Electronic Horn with Strobe5348 Single Tone Horn

Strona 73 - 6.2 Mapping Overview

Compatible Devices 151274-L8A-4Faraday(cont.)6300 Mini-Horn6301 Mini-Horn 6302 Mini-Horn6310 Mini-Horn/Strobe6311 Mini-Horn/Strobe6312 Mini-Horn/Strob

Strona 74 - 6.2.1 Input Point Mapping

IntelliKnight 5808 Installation Manual 151274-L8A-5FCI(cont.)S24110-FC StrobeS24110W-FC StrobeS24110K-FC StrobeFederal Signal450 HornVALS Horn/StrobeG

Strona 75 - 6.2.2 Output Circuit Mapping

Compatible Devices 151274-L8A-6Gentex(cont.)WGEC24-75WxxWeatherproof Horn/StrobeWGES24-75WxWeatherproof StrobeWGMS-24-X x x Horn/StrobeSystem SensorCH

Strona 76 - 6.2.3 Zone Event Mapping

IntelliKnight 5808 Installation Manual 151274-L8A-7System Sensor(cont.)PC4Rxx4-Wire Horn/StrobeP4RHxx4-Wire Horn/Strobe High CandelaP4Wxx4-Wire Horn/S

Strona 77

Compatible Devices 151274-L8A-8WheelockAH-12xHornAH-24xHornAH-12WPxHorn WeatherproofAH-24WPxHorn WeatherproofAMT-241575WxxMulti-Tone Horn StrobeAMT-24

Strona 78 - 6.2.4 Mapping LED Points

IntelliKnight 5808 Installation Manual 151274-L8A-9Wheelock (cont.)MTWPA-2475WxxMultitone Horn StrobeMTWPB-2475WxxMultitone Horn StrobeMTWPG-2475WxxMu

Strona 79 - To exit the programming menu:

IntelliKnight 5808 Installation Manual 151274-L82-32.2.3 Requirements for Local Protected Fire Alarm SystemsAt least one UL listed supervised notifica

Strona 80 - 6.4.4 Editing Keys

Compatible Devices 151274-L8A-10Wheelock (cont.)RSSWPG-24MCCHxStrobe Weatherproof RSSWPR-24MCCHxStrobe Weatherproof RSSWP-2475WxStrobe Weatherproof RS

Strona 81

IntelliKnight 5808 Installation Manual 151274-L8A-11A.2 Two-Wire Smoke DetectorsTable A-2 lists two-wire smoke detectors that are compatible with the

Strona 82

Compatible Devices 151274-L8A-12ESL 429C (S10A) N/A S10A 30 / loop429CRT (S11A) N/A S11A 30 / loop429CST (S11A) N/A S11A 30 / loop429CT (S10A) N/A S10

Strona 83

IntelliKnight 5808 Installation Manual 151274-L8A-13A.3 Compatible 520Hz Low Frequency BasesSystem Sensor 1400 A N/A 20 / loop1451 (B401B) A A 20 / lo

Strona 84

151274-L8B-1Appendix BSpecial Characters ListsThis section contains tables of programmable characters that may be used for device, module, and zone na

Strona 85

Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited

Strona 86

Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that th

Strona 87

Cut Along the Dotted LineP/N 151273-L8 Rev. C Model 5808 Basic Operating InstructionsThese Instructions must be framed and displayed next to th

Strona 88

Cut Along the Dotted Line

Strona 90

151274-L83-1Section 3Before You Begin InstallingThis section of the manual is intended to help you plan your tasks to facilitate a smooth installation

Strona 91

Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com

Strona 92

Before You Begin Installing 151274-L83-23.3 Electrical SpecificationsTable 3-1 list the terminal block on the 5808 as well as a description of the eac

Strona 93 - Programming

Installation ProcedureInstallation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING

Strona 94 - 7.2.1.2 Module, Wiring Class

IntelliKnight 5808 Installation Manual 151274-L83-33.4 Wiring SpecificationsInduced noise (transfer of electrical energy from one wire to another) can

Strona 95 - 7.3 Zone

Before You Begin Installing 151274-L83-43.5 Board Assembly Diagram Figure 3-2 Model 5808 AssemblyFigure 3-2 shows the circuit boards and annunciato

Strona 96 - 7.3.1.2 Edit Zone Properties

IntelliKnight 5808 Installation Manual 151274-L83-53.6 Calculating Current Draw and Standby BatteryThis section is for helping you determine the curre

Strona 97

Before You Begin Installing 151274-L83-6SK-Photo(99 max.)1Standby/Alarm: .30 mA6mA mASK-Photo-T mA mASK-Ion mA mASK-Heat

Strona 98 - 7.3.1.3 Zone Outputs

IntelliKnight 5808 Installation Manual 151274-L83-7SLC AccessoriesB200SR Sounder Base(99 max.)Aux Pwr Standby: .5 mA mAAlarm:

Strona 99

Before You Begin Installing 151274-L83-81. Total does not include isolator devices or accessory bases.2. If using door holders, you do not need to con

Strona 100 - 7.3.1.4 Cadence Patterns

IntelliKnight 5808 Installation Manual 151274-L83-9SD500-LED(40 max.)1Aux. Pwr Standby: 10 mA mAAlarm:

Strona 101 - 7.3.4 View Zone Points

Before You Begin Installing 151274-L83-101. Total does not include isolator devices or accessory bases.2. If using 24 VDC aux power only. No standby o

Strona 102 - 7.4.1.2 Edit Group Properties

IntelliKnight 5808 Installation Manual 151274-L83-113.7 Installation Tasks OverviewThis section provides a chart listing tasks that need to be perform

Strona 103 - SILENCE key will be ignored

Before You Begin Installing 151274-L83-12Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns all switches as

Strona 104 - 7.4.3 Delete Group

Contents1ContentsSection 1Introduction ...

Strona 105 - 7.4.4 View Group Points

151274-L84-1Section 4Control Panel Installation4.1 Mounting the Control Panel CabinetRead the environmental specifications in Section 3.2 before mount

Strona 106 - 7.5 Point

Control Panel Installation 151274-L84-24.2 AC ConnectionAt installation, connect the AC terminals to the power source as shown in Figure 4-1. It may b

Strona 107 - Table 7-5 Point Programming

IntelliKnight 5808 Installation Manual 151274-L84-34.3.1 RBB Accessory CabinetThe Model RBB Accessory cabinet can be used when your backup batteries r

Strona 108 - Programming 151274-L8

Control Panel Installation 151274-L84-43. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5.Figure

Strona 109

IntelliKnight 5808 Installation Manual 151274-L84-54.4 SBUS WiringThis section contains information on calculating SBUS wire distances and the types o

Strona 110

Control Panel Installation 151274-L84-6Note: The following formulas were used to generate the wire distance chart:Wiring Distance calculation example:

Strona 111 - Comments

IntelliKnight 5808 Installation Manual 151274-L84-74.4.2 Wiring ConfigurationsFigure 4-7 illustrates Class B configuration.Figure 4-7 SBUS Class B Wi

Strona 112

Control Panel Installation 151274-L84-84.5 5860 Remote Annunciator InstallationThe optional Model 5860 Remote Annunciator, shown in Figure 4-8, perfor

Strona 113 - 7.6.1.1 Edit Accounts

IntelliKnight 5808 Installation Manual 151274-L84-94.5.1 Mounting the 5860This section of the manual describes mounting the remote annunciator. The an

Strona 114

Control Panel Installation 151274-L84-10(See Figure 4-10 for location of the set screws.) Figure 4-10 Annunciator Back Box and Bezel Details4

Strona 115 - 7.6.1.2 Auto Test Time

Contents24.3 Battery Connection ...4-2

Strona 116 - 7.6.2.1 Dialing Prefix

IntelliKnight 5808 Installation Manual 151274-L84-11annunciator. Studs used with an electrical box must be two by fours (or larger).Figure 4-11 Place

Strona 117 - 7.6.3.1 Trouble Events

Control Panel Installation 151274-L84-124.5.1.2 Surface MountingThe 5860 can be mounted directly to a surface or can be attached to a single, double,

Strona 118 - 7.6.3.2 System Alarm Cadence

IntelliKnight 5808 Installation Manual 151274-L84-135. Connect a printer to the 5824 as shown in Figure 4-15. Figure 4-14 5824 Connection to the Pane

Strona 119 - 7.6.4.1 Water Flow Delay

Control Panel Installation 151274-L84-14• Select a name, if desired (see Section 7.2.1.1).• Select options for the printer and the output port. See be

Strona 120 - 7.6.4.3 Low AC Report Delay

IntelliKnight 5808 Installation Manual 151274-L84-15number. Figure 4-17 5880 Board Layout 4.7.2 FACP ConnectionThe 5880 connects to the panel via the

Strona 121 - 7.6.5.4 Plex Door Option

Control Panel Installation 151274-L84-164.7.3 LED WiringThere are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its powe

Strona 122 - 7.6.7 Edit Banner Message

IntelliKnight 5808 Installation Manual 151274-L84-174.7.4 Dry Contact WiringThe 8 input circuits on the 5880 board are for monitoring switch inputs-an

Strona 123 - 7.6.8 SLC Family

Control Panel Installation 151274-L84-184.8 5865-3 / 5865-4 LED Annunciator InstallationThe 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30

Strona 124 - 7.9 Access Codes

IntelliKnight 5808 Installation Manual 151274-L84-194.8.2 5865 MountingMount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a sta

Strona 125 - 7.9.1 Profile Edit Menu

Control Panel Installation 151274-L84-204.9 Configuring ModulesThis section describes how to configure any system hardware modules that have been adde

Strona 126 - 7.9.1.3 Panel Functions

Contents35.3 Maximum Number of Devices ...5-25.4 Wirin

Strona 127 - System Operation

IntelliKnight 5808 Installation Manual 151274-L84-214.10 Telephone ConnectionConnect the telephone lines as shown in Figure 4-26. The Model 7860 phone

Strona 128 - 8.3 Key Operation

Control Panel Installation 151274-L84-22Figure 4-27 Class B Notification Appliance Circuit Wiring4.11.1.2 Class A Notification WiringYou must use an

Strona 129 - 8.4 Menu System

IntelliKnight 5808 Installation Manual 151274-L84-232. Configure the circuit for Class A in programming (see Section 7.5).Figure 4-28 Class A Notific

Strona 130 - 8.5 Basic Operation

Control Panel Installation 151274-L84-24power is immediately restored to the door holder circuits. Figure 4-29 Example of an Auxiliary Power For Door

Strona 131 - 8.5.8 Conduct a Fire Drill

IntelliKnight 5808 Installation Manual 151274-L84-254.12 On-Board Programmable Relays (Conventional)The control panel has two built-in programmable re

Strona 132 - 8.5.13 Reset Alarms

Control Panel Installation 151274-L84-264. Program NAC circuit 2 for alarm.5. Program NAC circuit 1 for supervisory non latching.Note: NACs must be pr

Strona 133

IntelliKnight 5808 Installation Manual 151274-L84-27It is not possible to reset the remote indication until you clear the condition and reset the cont

Strona 134

Control Panel Installation 151274-L84-28rent using the potentiometer (R10) on the 5220 board. Normal loop current is 2-to-8 mA with a 1k ohm remote st

Strona 135 - 8.5.20 Working with a Printer

IntelliKnight 5808 Installation Manual 151274-L84-294. Program the output group characteristics as non-silenceable and reverse polarity. See Section 7

Strona 136 - 8.6 Operation Mode Behavior

Control Panel Installation 151274-L84-304.13.4 Using the SD500-ARM Addressable Relay ModuleWhen the SD500-ARM is wired for polarity reversal, it repor

Strona 137

Model 5808 Installation Manual47.3.2 Add Zone ...

Strona 138 - System Operation 151274-L8

IntelliKnight 5808 Installation Manual 151274-L84-314.13.5 Using a MR-201/T Control Relay From Air ProductsWhen the MR-201/T control relay is wired fo

Strona 139 - Operation

Control Panel Installation 151274-L84-324.13.6 Transmitter Activated by Dry ContactsThis section describes the connection of a UL 864 listed remote st

Strona 140

151274-L85-1Section 5SK and SD SLC Device Installation5.1 List of SK SLC DevicesThe following SK SLC devices can be used with the control panel. See t

Strona 141 - 8.7 Releasing Operations

SK and SD SLC Device Installation 151274-L85-25.2 List of SD SLC DevicesThe following SD SLC devices can be used with the control panel. See the appro

Strona 142

IntelliKnight 5808 Installation Manual 151274-L85-35.4.1 Wiring SLC in Style 4 (Class B) ConfigurationNo special wire is required for addressable loop

Strona 143

SK and SD SLC Device Installation 151274-L85-4must be met in addition to the maximum distance requirements for the various wire gauges.

Strona 144 - 8.8 Smoke Alarm Verification

IntelliKnight 5808 Installation Manual 151274-L85-5Note: No t-taps allowed on class A SLC loops.5.5 SK Detector InstallationThis section describes how

Strona 145 - Reporting

SK and SD SLC Device Installation 151274-L85-65.6 Addressing SK SLC DevicesAll SK devices are addressed using the two rotary dials that appear on the

Strona 146 - Reporting 151274-L8

IntelliKnight 5808 Installation Manual 151274-L85-75.8 Addressing SD DevicesThis section tells how to address detectors and modules.5.8.1 SD505-APS, S

Strona 147

SK and SD SLC Device Installation 151274-L85-85.8.2 SLC Devices with DIP SwitchesInput and relay module addresses are set using the DIP switches on th

Strona 148

Contents5Section 8System Operation ...

Strona 149

151274-L86-1Section 6Programming OverviewThis section of the manual is intended to give you an overview of the programming process. Please read this s

Strona 150

Programming Overview 151274-L86-21 using constant on output when an alarm condition occurs. Circuit 5 (Relay 1):Assigned to Group 124. JumpStart autom

Strona 151

IntelliKnight 5808 Installation Manual 151274-L86-37. Select one of the following options from the menu that displays. 1 - Review System Press 1 i

Strona 152

Programming Overview 151274-L86-46.2 Mapping OverviewThis section of the manual is an overview of mapping. Details about how to select mapping options

Strona 153

IntelliKnight 5808 Installation Manual 151274-L86-56.2.1 Input Point MappingInput points are assigned to input zones. Any input point can be assigned

Strona 154 - Testing and Troubleshooting

Programming Overview 151274-L86-66.2.2 Output Circuit MappingFigure 6-3 is a simple example showing how to assign notification and relay output circui

Strona 155

IntelliKnight 5808 Installation Manual 151274-L86-76.2.3 Zone Event Mapping There are 11 types of events that can occur in zones (see below). For each

Strona 156 - 10.3.2 SLC Multi Locator

Programming Overview 151274-L86-8Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns

Strona 157 - 10.3.3 I/O Point Control

IntelliKnight 5808 Installation Manual 151274-L86-96.2.4 Mapping LED PointsFigure 6-6 is a simple example showing how LED points are mapped to zones a

Strona 158

Programming Overview 151274-L86-106.3 Programming Using the 5660 Silent Knight Software SuiteYou can use the 5660 Silent Knight Software Suite (SKSS)

Strona 159 - Installation Records

Model 5808 Installation Manual610.2 Common Problems ...

Strona 160

IntelliKnight 5808 Installation Manual 151274-L86-116.4.2 Moving through the MenusFigure 6-8 shows how to move through Program Menu screens, using the

Strona 161 - Compatible Devices

Programming Overview 151274-L86-126.5 Programming Menu Quick ReferenceThis section of the manual lists all Program Menu options in the order they appe

Strona 162 - Compatible Devices 151274-L8

IntelliKnight 5808 Installation Manual 151274-L86-13Group1Edit Group Select Group to EditGroup Name Section 7.4.1.1Group PropertiesLatching Options*No

Strona 163

Programming Overview 151274-L86-14PointInternal and External 5815XL, SK DevicesSensor Point #UNUSEDSection 7.5.1DETECTORPHOTO, ION, HEAT,ACCLIMATEHEAT

Strona 164

IntelliKnight 5808 Installation Manual 151274-L86-15Point(cont.)Internal and External 5815XL, SK DevicesSensor Point #SUP DETPHOTO, ION, HEAT,ACCLIMAT

Strona 165

Programming Overview 151274-L86-16Point(cont.)Internal and External 5815XL, SK DevicesSensor Point #CO FIREALRM Fire/ALRM CO, ALRM Fire/SUPR CO, SUPR

Strona 166

IntelliKnight 5808 Installation Manual 151274-L86-17Point(cont.)Internal and External 5815XL, SK DevicesModule Point # DETECTOR 2WIRE SMK*Silenceable

Strona 167

Programming Overview 151274-L86-18Point(cont.)Internal and External 5815XL, SD DevicesPoint #SUP DETPHOTO, ION, HEAT*Latching (LA) or Non-Latching (NL

Strona 168

IntelliKnight 5808 Installation Manual 151274-L86-19Point(cont.)Internal and External 5815XL, SD DevicesPoint #SWITCHFIREDRILL, SILENCE, RESET*Silence

Strona 169

Programming Overview 151274-L86-20Point(cont.)Internal and External Power SupplyPoint #B SWITCHFIREDRILL, SILENCE, RESET*Silenceable (SI) or Non-Silen

Strona 170

151274-L81-1Section 1IntroductionThe 5808 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 86

Strona 171 - A.2 Two-Wire Smoke Detectors

IntelliKnight 5808 Installation Manual 151274-L86-21Point(cont.)5880Point #SWITCHSYS_AUX1, SUS_AUX2*Latching (LA) or Non-Latching (NL)Section 7.5.3*Si

Strona 172

Programming Overview 151274-L86-22System OptionsSystem Event OutputsTrouble EventsSystem TroubleSelect Group (*None)Section 7.6.3.1Select Cadence (*No

Strona 173 - Table A-3 Low Frequency Bases

IntelliKnight 5808 Installation Manual 151274-L86-23System Options(cont.)Daylight SavingsDST*Y (Enabled) or N (Disabled)Automatic Daylight Saving Time

Strona 174 - Special Characters Lists

151274-L87-1Section 7ProgrammingThis section of the manual describes how to manually program the control panel from the built-in annunciator. Each sub

Strona 175 - Advanced Replacement Policy

Programming 151274-L87-27.2.1 Edit ModulesThe features that can be edited when this option is selected are, module name, and class of wiring (Class A

Strona 176

IntelliKnight 5808 Installation Manual 151274-L87-32. Press 7 for Program Menu.3. Press 1 to enter module menu.4. Press 2 to add a module.5. From the

Strona 177 -

Programming 151274-L87-43. Press 2 to enter zone menu.4. Press 1 to edit a zone.5. Enter the zone number, then press ENTER.7.3.1.1 Edit Zone Name6. Pr

Strona 178 - Cut Along the Dotted Line

IntelliKnight 5808 Installation Manual 151274-L87-5Table 7-1 list the delay choices and a description of each.4. Press ENTER.Heat Temperature SettingU

Strona 179

Programming 151274-L87-67.3.1.3 Zone OutputsOutput groups and cadence patterns are mapped to events. They can be programmed to output when an event oc

Strona 180

IntelliKnight 5808 Installation Manual 151274-L87-7Zone Mapping ExampleSuppose you want to program Zone 1 so that:• Any alarm (detector, water flow or