Control Panel Installation 151274-L8
4-22
Figure 4-27 Class B Notification Appliance Circuit Wiring
4.11.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-28.
Caution
For proper system supervision do not use looped wire under terminals marked + and – of the Flexput connectors.
Break wire runs to provide supervision of connections.
Alarm Polarity Shown
UL Listed EOL
Model 7628
4.7 k
Supervised
Power Limited
Notification Wiring
Max. Impedance: 1.5