151295 1-1
Section 1
Introduction
The 5700 Fire Alarm Control / Communicator is an addressable fire control system that meets
the requirements of UL 864.
1.1 Overview of Basic System
The 5700 base system is 50 addressable point system with a built-in annunciator which can
also be used to program the system.
1.1.1 Hardware Features
• The 5700 panel has one signaling line circuit (SLC) that supports 50 addressable devices.
• 2.5A of output power is available through 2 sets of terminals for notification appliance
circuits or auxiliary applications. Each circuit is power limited per UL 864 and can source
up to 2.5A (total output power for both circuits must not exceed 2.5A).
• Built-in dual phone line, digital alarm communicator/transmitter (DACT).
• Reports events to central station by point or by zone.
• UL Listed for pre-action and deluge releasing systems.
• Two general purpose Form C programmable relays.
• One Form C Trouble Relay.
• Basic system operation can be performed from the on-board, or any remote annunciator.
• Up to 20 user profiles can be programmed, each having custom access code, and main
menu items.
• Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
• Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight
devices on one control panel. See Sections 4.7 and 4.8 for additional information on these
models.
• Printing of detector status, event history, and real time event log available through the
Model 5824 Serial / Parallel Interface (sold separately).
• 125 software zones, 125 output groups.
• Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight
5895XLs per system). See note below.
• Add 4 Notification/Auxiliary power circuits with each 5496 Intelligent Power Module (up
to eight 5496s per system). See note below.
Note: The system can support a maximum of eight intelligent power modules, either the 5895XL or 5496, in any
combination.