SILENT KNIGHT 5700 Dokumentacja Strona 101

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 100
Programming
151295 7-9
Example or Zone Mapping:
Suppose you want to program Zone 1 so that:
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the
ANSI cadence pattern.
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output
groups. Figure 7-4 shows how you would program this application.
Figure 7-4 Zone Mapping Example
Przeglądanie stron 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 185 186

Komentarze do niniejszej Instrukcji

Brak uwag